Motor Starting
Sizing of Generators for Motor Starting (Direct on Line)
Assumptions
For Motors up to 200kW
6-7 times running current on start up of motor
Efficiency 90% (0.9) PF 0.85
For motors above 200kW
5-6 times running current on start up of motor
Efficiency 95% (0.9) PF 0.85
Allowance
Average transient voltage trip will be around 15% of rated kW of alternator. Allow max. 35% voltage dip on main input terminals on capital load.
25% for voltage dip 10% for VHz engine dip
Note: contactors may start to "drop out" at around 75% rated voltage.
Check voltage dip and locked rotor kVA curve on spec sheet for relevant alternator and multiply running kVA by assumed starting current multiplier to give starting (locked rotor) kVA.
Approximate current per line or phase taken at full rated HP by motors of average efficiency and power factor.
| Motor Rating | Direct Current | Alternating Current | |||||
| 110V | 220V | 550V | 240V | 380V | 415V | 550V | |
| HP | Amp | Amp | Amp | Amp | Amp | Amp | Amp |
| 0.5 | 5.7 | 2.8 | 1.1 | 3 | |||
| 1 | 10 | 5 | 2 | 6 | 1.9 | 1.7 | 1.3 |
| 2 | 18 | 9 | 3.6 | 10 | 3.6 | 3.3 | 2.5 |
| 3 | 26 | 13 | 5.2 | 15 | 5.1 | 4.6 | 3.5 |
| 5 | 42 | 21 | 8.4 | 24 | 8 | 7.3 | 5.5 |
| 7.5 | 60 | 30 | 12 | 35 | 11.6 | 10.6 | 8 |
| 10 | 80 | 40 | 16 | 46 | 15.1 | 13.8 | 10.4 |
| 15 | 117 | 59 | 23 | 67 | 22 | 20 | 16 |
| 20 | 154 | 77 | 31 | 88 | 29 | 27 | 21 |
| 25 | 190 | 95 | 38 | 110 | 37 | 34 | 26 |
| 30 | 227 | 114 | 46 | 130 | 43 | 40 | 30 |
| 40 | 300 | 150 | 60 | 180 | 59 | 54 | 41 |
| 50 | 375 | 187 | 75 | 210 | 73 | 67 | 50 |
| 50 | 445 | 223 | 89 | 253 | 87 | 80 | 60 |
| 60 | 520 | 260 | 104 | 291 | 102 | 94 | 70 |
| 80 | 600 | 300 | 120 | 332 | 117 | 107 | 81 |
| 100 | 740 | 270 | 148 | 412 | 145 | 133 | 100 |
| 125 | 460 | 184 | 545 | 181 | 166 | 125 | |
| 150 | 220 | 217 | 199 | 150 | |||
| 175 | 256 | 253 | 232 | 175 | |||
| 200 | 292 | 288 | 264 | 199 | |||
| 250 | 353 | 323 | 244 | ||||
| 300 | 421 | 385 | 291 | ||||
Technical Info
- Hire Fleet Cable / Generator Size
- Ratings of Generators
- Capacitive Load (capacitors, cable)
- Calculating kVA Single Phase
- Calculating kVA & kW (Three Phase)
- Generator Formulae (Three Phase Generators)
- Single Phase Generators (and DC)
- KVA/AMPERE Data
- Motor Starting On-Line
- Motor Starting
- Voltage Drop Calculations
For more information contact us now on 0800 146 763 or e-mail info@sldpumpspower.co.uk